Search our website
Dwyer Omega – Series APM-MPM-PPM 1/8 DIN Digital Panel Meter, Dual Display, 4-20 mA/0-10 V, NEMA 4X
Click to enlarge

Dwyer Omega – Series APM-MPM-PPM 1/8 DIN Digital Panel Meter, Dual Display, 4-20 mA/0-10 V, NEMA 4X

Dwyer Omega – Series APM-MPM-PPM 1/8 DIN Digital Panel Meter, Dual Display, 4-20 mA/0-10 V, NEMA 4X

Product Code: Series APM MPM PPM

Manufacturer: Dwyer Omega


These 1/8 DIN digital panel meters accept signals from various transmitters and flowmeters and displays them on a six-digit, dual line display in engineering units. These meters will also provide power to the field device and include a NEMA 4X front panel. Free, USB based programming software is resident on the meter. Options include up to four relays and a 4-20 mA output.

The Series MPM Dual Line Configurable Panel Meter is a general purpose process meter that is field selectable for a 4-20 mA or 0-10 V input signal. It provides 24 VDC to power the transmitter. The dual line display can display the process variable on the upper line and engineering units on the lower line. Or, in dual scale mode, the process variable can be displayed in one units (like height) on the upper display and another (like volume) on the lower display. The meter also has an automatic Round Horizontal Tank function a well as 32 point linearization.

The Series APM Dual Line Configurable Panel Meter and Series PPM Dual Line Configurable Panel Meter are flow / rate totalisers for analog or pulse inputs. The most useful feature of these products is their dual line display which allows rate and total to be displayed at the same time. A non-resetable grand total can also be programmed. Total can be reset either from the front panel or by connecting a remote switch to the F4 terminal at the rear of the meter. The Series APM accepts either a 4-20 mA or 0-10 V input signal and provides the 24 VDC to power the flowmeter. Other features of the APM include square root extraction for DP flow, and programmable exponents for open channel flow. The Series PPM accepts a pulse input signal and provides either 5, 10 or 24 VDC to power the flowmeter. Adding the 4-20 mA output option converts the pulse into a signal that can be run long distances to a PLC or other device.

Accuracy

± 0.03 %

Accuracy Detail

± 0.03% of calibrated span ± 1 count

Compliance

CE, UL

Display Note

Red LED, Dual-line 6-digit display, 0.60 in and 0.46 in

Display Type

LED

Enclosure Ratings

IP65, NEMA Type 4X

Excitation Voltage

24 Vdc

Impedance Input

50 to 100 Ω

Input Note

APM and MPM: 0-20 mA, 4-20 mA, 0-5 V, or ± 10 V inputs; PPM: Field selectable: Pulse or square wave 0-5 V, 0-12 V, or 0-24 V @ 30 kHz; TTL; open collector 4.7 k Ω pull-up to 5 V @ 30 kHz; NPN or PNP transistor, switch contract 4.7 k Ω pull-up to 5 V @ 40 Hz. Input impedance: 50 to 100 Ω.

Number of Digits

6

Operating Temperature, Max

65 °C

Operating Temperature, Min

-40 °C

Software

Free, USB based. Resident on meter, nothing to download

Storage Temperature, Max

85 °C

Storage Temperature, Min

-40 °C

Time Delay

0 to 999.9 s

Time Delay Note

0 to 999.9 s, on and off relay time delays; programmable and independent for each relay

Weight

9.5 oz

  • Three levels of password protection
  • Math functions for flow & round horizontal tanks
  • 32-point linearization, square root or programmable exponent
  • Multi-pump alternation control
Datasheet Download
Instruction Manual Download
MPM, APM, PPM, & LTI Series Modbus® Register Tables Download

The new way to pay from Process Instrument Solutions.

Similar Products